- Measure
31,520 GPD peak-demand support and approximately $229,000/year commercial OPEX reduction. The 90% flux-recovery and 0.26–0.39 NTU observations belong to the separate 2018 filtration supplier vendor study.
- Food-safety installation review
The Food Safety sheet of Equipment Purchase and Installation Safety Checklist.xlsx records engineering review/signoff by for ceramic membrane Crossflow 17.42, the feed manifold, the permeate manifold and Freshwater Tank V-56 in the Bulk / Drumming Warehouse. This adds installation-review scope, not sterile-process certification.
- Sanitary and aseptic: Controlled case details
Coordinated ceramic-crossflow architecture, TMP and flow control, backflush, product recovery, timed chemical dosing, heated caustic circulation, cooling, rinsing, automated sequences, utilities, and controls.
- Sanitary and aseptic: Controlled case details
31,520 GPD peak-demand support.
- Sanitary and aseptic: Controlled case details
Approximately $229,000/year OPEX reduction.
- Vendor system architecture
The filtration supplier system architecture describes: Chemical tanks: TK-B5 HYPO 200 L, TK-B3 CAUSTIC 200 L, TK-B4 ACID 200 L.
- Vendor system architecture
The filtration supplier system architecture describes: Feed/circulation tank TK-01: 820 L.
- Vendor system architecture
The filtration supplier system architecture describes: Permeate/backflush tank T2: 100 L.
- Vendor system architecture
The filtration supplier system architecture describes: ceramic membrane module M0001; heat exchanger HE30; pumps P01, P02, P03, and chemical pump P80.
- Vendor system architecture
The filtration supplier system architecture describes: P&ID labels STEAM 1 BARG; CP-07 condensate callout includes 1-2 barg and 1.500 litros/hora; another 1.500 litros/hora callout appears near CP-09 retentate recovery.
- Vendor system architecture
The filtration supplier system architecture describes: Slide 2: concentrate-side tag group 01-19; TK01 as feed buffer/circulation tank; P01 controls FIT11; lower/higher circulation changes loop-to-tank concentration relationship; CV08 controls PIT01; P02 provides approximately 5 m/s crossflow.
- Vendor system architecture
The filtration supplier system architecture describes: Slide 3: permeate/backflush tag group 50-59; FCV01.1 controls flow or TMP; P03 sends filtrate to final tank and backflushes; AV51/56 close during backflush; T2 backflush volume is deducted from filtrate and returns to TK01.
- Vendor system architecture
The filtration supplier system architecture describes: Slide 4: chemical tags 80-89; chemical dosing by time; each dose followed by AV82/AV89 water flush; utility group stated as 30 to 29, an internal source error; temperature uses minimum/maximum hysteresis.
- Vendor system architecture
The filtration supplier system architecture describes: Slide 5: source calls system totally automatic with low operator intervention; skid exchanges requests/confirmations with peripheral equipment but explicitly does not control the peripheral plant.
- Vendor system operating description
The filtration supplier system operating description records: Slide 6: workstream hierarchy includes start/play, steps, phases, auxiliary sub-phases, stop, and end-of-workstream logic.
- Vendor system operating description
The filtration supplier system operating description records: Slide 7: production sequence starts full of water, then forced/gravity drains on permeate and concentrate sides, TK01 raw-vinegar fill, concentrate/permeate fill, filtration/concentration, final concentration, permeate/concentrate recovery, and cold-water rinse.
- Vendor system operating description
The filtration supplier system operating description records: Slide 8: system full-of-water starting state.
- Vendor system operating description
The filtration supplier system operating description records: Slide 9: forced permeate drain uses AV56/76/54/65, FCV01.1 at 100 percent, P03 at 50 percent; ends by maximum time, T2 minimum level, or LSL-02.
- Vendor system operating description
The filtration supplier system operating description records: Slide 10: gravity permeate drain adds AV58, FCV01.1 at 100 percent, P03 off; ends after LSL-02 delay.
- Vendor system operating description
The filtration supplier system operating description records: Slide 11: forced concentrate drain uses AV03/01/62, P01 at 50 percent; ends by maximum time, TK01 minimum, or LSL-01.
- Vendor system operating description
The filtration supplier system operating description records: Slide 12: gravity concentrate drain uses AV03/01/62/05/04, CV08 at 100 percent, P01 off; ends after LSL-01 delay.
- Vendor system operating description
The filtration supplier system operating description records: Slide 13: fill TK01 with product using AV11/03; ends at TK01 level setpoint.
- Vendor system operating description
The filtration supplier system operating description records: Slide 14: fill concentrate side using AV03/01/05, CV08 at 20 percent, P01 at 50 percent; ends when TK01 level stops changing.
- Vendor system operating description
The filtration supplier system operating description records: Slide 15: concentrate circulation uses AV03/01, CV08 at 20 percent, P01 at 50 percent and P02; ends by time delay.
- Vendor system operating description
The filtration supplier system operating description records: Slide 16: fill permeate side using AV03/01/56, CV08 at 20 percent, FCV01.1 at 10 percent, P01 at 50 percent and P02; ends at T2 level setpoint.
- Vendor system operating description
The filtration supplier system operating description records: Slide 17: filtration uses AV03/01/56/51, CV08, FCV01.1, P01/P02/P03; P01 controlled by FIT11; P03 by LIT02; CV08 by PIT01; FCV01.1 starts on FIT01.1 then switches to pressure control at TMP setpoint.
- Vendor system operating description
The filtration supplier system operating description records: Slide 18: low LIT01 opens AV11; high setpoint closes AV11.
- Vendor system operating description
The filtration supplier system operating description records: Slide 19: P02/circulation heats product; high TT02 opens AV32/34 cooling; low TT02 closes AV32/34.
- Vendor system operating description
The filtration supplier system operating description records: Slide 20: timed production backflush closes AV51 and stops P03; T2 fills high; AV56/FCV01.1 close; P03 approximately 100 percent; after approximately 5 seconds AV58 opens and consumes almost all T2; filtration resumes.
- Vendor system operating description
The filtration supplier system operating description records: Slide 21: filtration ends on maximum time/volume, maximum DPM PIT02-PIT01, maximum TMP, maximum TT02, minimum flow in TMP control indicating clogged membrane, or minimum flow with low TK01 and AV11 open indicating empty customer feed tank.
- Vendor system operating description
The filtration supplier system operating description records: Slide 22: final-concentration purpose is to limit final loss to loop volume.
- Vendor system operating description
The filtration supplier system operating description records: Slide 23: final concentration ends on TK01 low-low, maximum time, maximum DPM/TMP/temperature, or minimum filtration flow.
- Vendor system operating description
The filtration supplier system operating description records: Slide 24: permeate recovery uses AV56/54/51/76, FCV01.1, P03 fixed speed; ends by maximum time, T2 minimum, or LSL-02.
- Vendor system operating description
The filtration supplier system operating description records: Slide 25: concentrate recovery uses AV03/04/05/08, CV08, and source text says P03 fixed speed; end references LSL-01 at P01 suction.
- Vendor system operating description
The filtration supplier system operating description records: Slide 26: cold-water rinse fills feed/concentrate/permeate, circulates concentrate/permeate, performs forced/gravity drains, refills, and shows Repeat x2 with visually ambiguous bracket scope.
- Vendor system operating description
The filtration supplier system operating description records: Slide 27: cold-water fill TK01 via AV71; ends at TK01 setpoint.
- Vendor system operating description
The filtration supplier system operating description records: Slide 28: cold-water concentrate fill uses AV03/01/05, CV08 20 percent, P01 50 percent; ends when TK01 level stops changing.
- Vendor system operating description
The filtration supplier system operating description records: Slide 29: cold-water permeate fill uses AV03/01/56, FCV01.1 10 percent, P01 50 percent; ends at T2 setpoint.
- Vendor system operating description
The filtration supplier system operating description records: Slide 30: cold-water concentrate circulation uses AV03/01, CV08 30 percent, P01 50 percent and P02; time-delay end.
- Vendor system operating description
The filtration supplier system operating description records: Slide 31: cold-water permeate circulation uses AV03/01/59, CV08 30 percent, P01 50 percent and P02; time-delay end.
- Vendor system operating description
The filtration supplier system operating description records: Slide 32: cold-water backflush closes AV59; T2 fills high; AV76/FCV01.1 close; P03 approximately 100 percent; after approximately 5 seconds AV58 opens; AV59 reopens.
- Vendor system operating description
The filtration supplier system operating description records: Slide 33: TK01 flush fills T2 high, closes AV76/FCV01.1, runs P03 approximately 50 percent, waits approximately 5 seconds, opens AV70/77, and consumes almost all T2.